Function type for each function block instance in private range is selected with
parameter FunctionType. Default values are defined in private range 1 - 4. One for
each instance.
Information number must be selected for each output signal. Default values are 1 - 8.
Info. no. Message Supported
1 Output signal 01 Yes
2 Output signal 02 Yes
3 Output signal 03 Yes
4 Output signal 04 Yes
5 Output signal 05 Yes
6 Output signal 06 Yes
7 Output signal 07 Yes
8 Output signal 08 Yes
4.2.4 Function commands generic for IEC 60870-5-103
I103GENCMD
4.2.4.1 Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
4.2.4.2 Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 18: I103GENCMD function block
4.2.4.3 Signals
Table 34: I103GENCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of command
Table 35: I103GENCMD Output signals
Name
Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON
1MRK 511 243-UEN - Section 4
IEC 60870-5-103 vendor specific implementation
650 series 45
Communication Protocol Manual